6ES7321-1BH02-4AA1 Siemens PLC Module 6ES73211BH024AA1
1
2
views: 346

6ES7321-1BH02-4AA1 Siemens PLC Module 6ES73211BH024AA1

Rate:
0.0000/5

( 0 reviews )

Item NO.: V000053 MOQ: 0
Weight:    0kgs
Package Size:  
 Price:
$0.00
 Qty:
      $0.00
 Shipping:   Calculate Shipping Cost

ZZC


General information
Hardware function status 01
Firmware version, V3.3
Parasian package
The ● engineering system above STEP 7 V5.5 + SP1 or above STEP 7 V5.2 + SP1 comes with HSP 218
supply voltage
rating,(DC)
● DC 24 V is
Allowed range, lower limit (DC) 19.2 V
Allowed range, upper limit (DC) of 28.8 V
External safe (recommended) * Minor 2 A
Power supply and voltage open circuit span
The ● blackout / outage span time is 5 ms
● repetition rate, with a * small value of 1s
input currenton
Consumption current (rated value) is 650 mA
Consumption current (no-load), with a typical value of 140 mA
On current, with a typical value of 3.5 A
I2t 1 A2·s
power loss
Power loss, with a typical value of 4 W
memorizer
work storage
● ensemble 32kbyte
● Exable No
The residual memory size for the remaining data module is 32 kbyte
Load the memory
The ● plug-in type (MMC) is
● Plug-In (MMC), * Large value of 8 Mbyte
Data management on the ● MMC (after the last programming), with a * small value of 10 y
buffer
● exists is; secured by MMC (maintenance-free)
● without battery is; program and data
CPU-handling time
For bit operations, the typical value is 0.1s
For word operations, the typical value is 0.24s
For fixed-point operations, the typical value is 0.32s
For floating-point operations, the typical value is 1.1s
CPU-assembly
Number of components (total) 1 024; (DB, FC, FB); the * large number of mount blocks can be reduced by the installed MMC.
DB
Number of ●, * large value of 1,024; number bar: 1 to 16,000
● capacity, * large value of 32 kbyte
FB
Number of ●, * large value of 1 024; number bar: 0 to 7999
● capacity, * large value of 32 kbyte
FC
Number of ●, * large value of 1 024; number bar: 0 to 7999
● capacity, * large value of 32 kbyte
OB
The ● description sees the action list
● capacity, * large value of 32 kbyte
Number of ● cycle OB available 1; OB 1
● time alarm OB number 1; OB 10
● delay alarm OB number 2; OB 20,21
● wake-up warning OB number 4; OB 32,33,34,35
● process alarm OB number 1; OB 40
● startup OB number 1; OB 100
● asynchronous error OB number 4; OB 80,82,85,87
● synchronization error OB number 2; OB 121,122
Nested depth
● per priority level of 16
Additional level 4 in the ● error OB 
Counters, timer, and their leftovers
S7 Counter
Number of ●: 256
residual magnetism
- -Adjustable, it is
-Lower limit 0
— An Upper Limit of 255
— From Z 0 to Z 7 is preset
counter range
-Lower limit 0
— Upper limit of 999
IEC, counter
The presence of ● is
● type SFB
No quantity of ● (restricted only by RAM)
S7, time
Number of ●: 256
residual magnetism
- -Adjustable, it is
-Lower limit 0
— An Upper Limit of 255
— No remaining is preset
time frame
— Lower limit of 10 ms
— Limit of 9,990s
IEC, calculagraph
The presence of ● is
● type SFB
No quantity of ● (restricted only by RAM)

Data range and its residual magnetic material
Keep the data range, all all (including tags, time, counters)
tab
Number of ●, with a * large value of 256 byte
● has left magnetic is; MB 0 to MB 255
● presets magnetic MB 0 to MB 15
● timing tag number of 8; 1 marker bytes
Data components
● adjustable residual is; feature not maintained in DB 
● preset magnetic magnetic is
Local data
● per priority, * 32 kbyte; * 2 KB
Address range
Peripheral address range
● Input side 1 024 byte
● output terminal 1 024 byte
Process image
● Input side 1 024 byte
● output terminal 1 024 byte
● input, adjustable for 1 024 byte
● output, adjustable for 1 024 byte
● input, 128 byte preset
● output, 128 byte preset
digital channel
● Input End 256
— Centralized formula 256
● Output End 256
— Centralized formula 256
analog channel
The ● input terminal 64
— Concentration No.64
● Output End 64
— Concentration No.64
Hardware expansion
Number of extended scaffolds, with a * large value of 0
Number of DP main stations
● ensemble 0
● is all about CP 4
Number of operational FM and CP's (recommended)
● FM 8
● CP, PtP 8
● CP,LAN 4
Component carrier
● component vector, * large value 1
● of components per component carrier, * large value 8
time
clock
The ● software clock is
● is buffered and synchronized, no; buffered, no; synchronizable, yes
● daily deviation, * large value of 10s; typical value: 2s
The display of the clock after the ● power supply, the clock is still displayed normally when the power is switched off
running time counter
● quantity 1
● number / number bar 0
 31 Times Hours of the ● value domain 0 to 2 (when using SFC 101)
The ● interval size is 1 h
● remaining is; you must restart every restart
time lock
● provides support is
The ● is on the MPI, and the main station is
The ● is on the MPI, and the slave station is
The ● is in the AS, and the main station is
● is in AS, stand No
digital input
Number of digital input terminals, 0
numeric output
Number of digital output terminals: 0
analog input
Number of analog inputs, 0
analog output
Number of analog output terminals, 0
joggle
Number of industrial Ethernet interfaces 0
Number of PROFINET interfaces, 0
Number of RS 485 interfaces 1; MPI
Number of RS 422 interfaces, 0
1. Interface
Interface type is integrated RS 485 interface
Physical composition of the RS 485
No potential isolation
Power supply at the interface (15 to 30 V DC), * Large value of 200 mA

 
No comment